Below-grade waterproofing

Waterproofing vs. Dampproofing Below Grade in Utah

Dampproofing and waterproofing are not interchangeable. How to tell which one a Utah foundation needs, and where below-grade systems usually fail.

Foundation wall with a waterproofing membrane applied before backfill

On a set of construction drawings, “dampproofing” and “waterproofing” can look like a one-word difference. Below grade, they are two very different levels of protection — and choosing the wrong one is one of the most expensive mistakes an owner can make, because the membrane is buried the day the backfill goes in.

This article explains the difference, when each one is appropriate, and the details that decide whether a below-grade system stays dry in Utah conditions.

The short answer

Dampproofing slows the movement of moisture vapor through a wall. It is typically a thin bituminous coating sprayed or rolled onto the outside of the foundation. It is not designed to resist liquid water under pressure.

Waterproofing is a membrane system designed to keep out liquid water, including water pushing against the wall under hydrostatic pressure. It is thicker, continuous, and detailed at every corner, joint and penetration.

If the space below grade will be occupied, finished, used for parking, or house mechanical and electrical equipment, it should be waterproofed.

Why the difference matters

Soil holds water. After a storm, during spring snowmelt, or anywhere the water table sits close to the bottom of the foundation, water builds up against the wall. That water has weight, and its pressure increases with depth. A dampproofing coating was never designed for that load; a waterproofing membrane was.

When dampproofing is asked to do a waterproofing job, the first sign is usually efflorescence — white mineral deposits on the inside face of the wall — followed by damp spots at cold joints and tie holes, and finally active leaks. By then the wall is backfilled and the fix is either excavation or interior injection.

See it in section

Why dampproofing is not enough.

  1. 01 / 06

    Groundwater rises

    After storms and snowmelt, water in the soil pushes against the wall. That push is hydrostatic pressure.

  2. 02 / 06

    Dampproofing alone

    A thin dampproofing coat slows soil moisture, but it is not built for water under pressure. Water finds cracks and joints.

  3. 03 / 06 GXS

    Waterproofing membrane

    A continuous membrane bonded to the wall and wrapped onto the footing resists water under pressure.

  4. 04 / 06 GXS

    Drainage board

    A dimpled board protects the membrane during backfill and gives water a clear path down.

  5. 05 / 06

    Footing drain

    A perforated drain at the footing carries the water away, so the pressure on the wall drops.

  6. 06 / 06

    Backfill & grade

    Backfill and a grade that slopes away from the building finish the system. The basement stays dry.

Utah conditions that push a project toward waterproofing

  • Shallow groundwater. Low-lying areas along the Jordan River corridor and near the Great Salt Lake can have water close to the surface, and seasonal levels rise with snowmelt.
  • Clay soils. Fine-grained soils drain slowly and hold water against foundation walls long after the surface has dried.
  • Snowmelt and irrigation. Spring runoff and landscape irrigation next to buildings both put water directly against the wall.
  • Deep basements and parking levels. Multifamily and mixed-use projects in Salt Lake City, Draper, Lehi and Provo increasingly include one or more parking levels below grade, which puts more of the structure below the water line.

A geotechnical report will usually describe groundwater conditions. If it notes groundwater within a few feet of the lowest slab, or if the design includes occupied space below grade, plan on waterproofing.

The main families of below-grade waterproofing

There is no single best product. The right system depends on access, pressure, schedule and budget.

SystemWhere it fits
Fully adhered sheet membranesPositive-side walls with good access; uniform factory thickness
Fluid-applied membranesComplex geometry and many penetrations; seamless
Pre-applied (blindside) membranesWalls poured against shoring where the outside face is never reachable
Bentonite compositesBelow-slab and blindside conditions with confinement
Crystalline systemsWaterproofing the concrete itself, as an admixture or surface treatment

Most commercial projects combine more than one: for example, a blindside membrane on the shoring walls, an under-slab membrane, and a crystalline admixture in an elevator pit.

Where below-grade systems actually fail

In our experience, membrane fields rarely fail on their own. Leaks almost always begin at the details:

  1. Penetrations — pipes, conduits and sleeves through the wall or slab.
  2. Form-tie holes — every tie is a potential path for water.
  3. Cold joints — the joint between the footing and wall, or between pours.
  4. Transitions — wall to slab, blindside to positive side, below grade to above grade.
  5. Terminations at grade — where the membrane ends and the above-grade wall begins.
  6. Backfill damage — membranes punctured before the protection course is installed.

That is why a good installer flashes and details the corners, penetrations and joints first, and installs the field membrane second.

Waterproofing an existing building

When water is already coming in, excavating to reach the outside of the wall is slow, disruptive and expensive. In most cases the leak can be stopped from the inside:

  • Polyurethane injection fills leaking cracks, joints and tie holes with a water-reactive resin that expands and seals the path.
  • Crystalline treatments applied to the interior face can reduce seepage through porous concrete.
  • Interior drainage and membrane systems manage water that cannot be stopped at the wall.

See our waterproofing service for how we handle existing buildings.

What to ask before you specify

  • What does the geotechnical report say about groundwater?
  • Will the space below grade be occupied, finished, or used for parking or equipment?
  • Is the wall formed against shoring (blindside) or excavated and backfilled (positive side)?
  • Which manufacturer warranty is required, and does the installer hold the certification to provide it?
  • Who is responsible for the transition between the below-grade membrane and the above-grade air barrier?

That last question matters more than most people expect. When one contractor owns both sides of that transition, it is far less likely to be missed.

The bottom line

Dampproofing is a moisture retarder. Waterproofing is a barrier against liquid water under pressure. For occupied space below grade in Utah, specify waterproofing, choose a system that fits the access and conditions, and make sure the details are installed by a certified crew.

If you have a project in design or a foundation that is already leaking, send us the drawings or photos and our estimating team will recommend a system.

Frequently asked questions

Is dampproofing enough for a basement in Utah?

Only where there is no chance of water under pressure against the wall and the space below grade is not occupied or finished. Occupied basements, parking levels and elevator pits should be waterproofed.

Does the building code require waterproofing?

Building codes require waterproofing where a high water table or severe soil-water conditions are known to exist, and dampproofing elsewhere. Project specifications and the use of the space often call for waterproofing even where the code minimum is dampproofing.

Can you fix a leaking foundation from the inside?

Yes. Most leaks through cracks, cold joints and tie holes can be stopped from the inside with polyurethane injection, which avoids excavation.